Description
Building types that benefit from the use of CAFCO® 300 include a wide range of educational, leisure and entertainment centres, and commercial projects.
GENERAL TECHNICAL PROPERTIES
| Fire resistance | Steel structures protected with CAFCO® 300 have undergone fire resistance tests up to 240 minutes in approved independent laboratories to recognised standards throughout the world, including:
Fire resistance test results relate solely to the constructions tested and test conditions imposed. |
|
|---|---|---|
| Spread of flame (as defined by building regulations) | Class 0 | |
| Alkalinity | pH | 8.0~8.5 |
| Thermal conductivity | W/m°K | 0.078 |
| Theoretical coverage at 15mm thickness | m²/tonne | 217 |
| Number of coats | One or more as required | |
| Cure | By hydraulic set | |
| Initial set at 20°C and 50% RH | 10~15 hours without accelerator | |
| Density (ASTM E605: 1993) | kg/m³ | 310 ± 15% without accelerator 310 – 10% (approximate) with accelerator |
| Bond impact (ASTM E760: 1992-2005) | No cracks or delaminations | |
| Air erosion resistance (ASTM E859: 1993-2006) | No erosion | |
| Compressive strength (ASTM E761: 1992-2005) | kg/cm² | 1.22 |
| Deflection effect (ASTM E759: 1992-2005) | No spalling, delamination or cracking | |
| Corrosion resistance | Does not promote corrosion of steel and does not require application over primed steel. Please seek advice of qualified structural engineer concerning long term corrosion protection. | |
| Colour and texture condition | Off-white with a monolithic spray texture |